Blists Hills

Blists Hills Victorian Town

The project: 

Chimney & Canopy Systems engineers worked closely with the M&E contractor to provide a solution to an awkward plant room layout serving 2 No. cascade condensing boilers.

A conventional B23 flue system was chosen for this installation due to the maximum flue length for a concentric room sealed flue system being only 7m.

Each primary flue system connected from the boilers into a common 250mm internal diameter header system which travelled around the plant room at high level before passing though the wall then turning vertically and passing through the roof to termination.

The flue system installed was our single wall fully welded 316 grade stainless steel, complete with joint seals and locking bands for use with condensing appliances.

Due to a conventional flue system being installed a high and low level ventilation system was required. As space was a premium a mechanical system was selected consisting of a 300mm diameter low level supply duct and a 225mm diameter high level both complete with axial fan, interlock, internal grilles and external all-weather louvres.

For more information, or if we can help with a project that you are working on at the moment, please contact our team of engineers on the following: